Communications configuring
3-100 System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
3.7.4 Tables
3.7.4.1 Address parameters, FMS utilities
Data to be configured:
kkkkkkkk:
Channel name, max. 8 characters, the first character must be a letter.
nnnnn:
PROFIBUS index, max. 5 characters
permissible value range for local objects (channel name):
6000..6199
permissible value range for remote objects (address stage 2):
17..65535
nnmm:
two communication references, each 2 digits
value range: 02..99
00 may also appear at the first position
Generated data:
kkkkkkkkbbbbbbpd: local object name, comprising:
kkkkkkkk:
Channel name, supplemented to 8 character by underline
bbbbbb:
Subrack name supplemented to 6 characters with underline
p:
CPU number, 1 digit: 1..8
d:
SIMADYN D communications utility, 1 letter:
P: Process data
M: Message system