Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-219
Edition 12.2003
NOTE
• The maximum number of interconnections of different inputs which
are changed with BICO technology, which are saved in the change
memory, are, for
− technology module T400: approx. 1600
− Application module FM 458: approx. 400
− CPU module in the SIMADYN D subrack: approx. 400
• Using BICO- technology, you can only change existing
interconnections between block I/O, but you cannot delete them.
• Using BICO technology, you cannot establish a new
interconnection at inputs which are not connected.
• Changes made to the interconnections of block I/O using BICO
technology, are only effective when updating the project in the CFC,
if they were saved.
• For changes made to the interconnections of block I/O using BICO
technology, when type checking the connections, the same rules
apply as for CFC.
!
CAUTION
The pseudo comment @DATX is not supported by the CFC test mode.
When changing an interconnection, where @DATX is available as
pseudo comment at the block input, the value for this connection is
updated again, but still maintaining the data consistency mechanisms.
Thus, the pseudo comment @DATX is no longer valid.
Remedy: Re-compile and re-load the user program.