EasyManua.ls Logo

Siemens D7-SYS - Page 308

Siemens D7-SYS
534 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-219
Edition 12.2003
NOTE
The maximum number of interconnections of different inputs which
are changed with BICO technology, which are saved in the change
memory, are, for
technology module T400: approx. 1600
Application module FM 458: approx. 400
CPU module in the SIMADYN D subrack: approx. 400
Using BICO- technology, you can only change existing
interconnections between block I/O, but you cannot delete them.
Using BICO technology, you cannot establish a new
interconnection at inputs which are not connected.
Changes made to the interconnections of block I/O using BICO
technology, are only effective when updating the project in the CFC,
if they were saved.
For changes made to the interconnections of block I/O using BICO
technology, when type checking the connections, the same rules
apply as for CFC.
!
CAUTION
The pseudo comment @DATX is not supported by the CFC test mode.
When changing an interconnection, where @DATX is available as
pseudo comment at the block input, the value for this connection is
updated again, but still maintaining the data consistency mechanisms.
Thus, the pseudo comment @DATX is no longer valid.
Remedy: Re-compile and re-load the user program.

Table of Contents

Related product manuals