LMVSeriesTechnicalInstructions
DocumentNo.LV51000
SCCInc. Page23 Section6
NumberTauSuspend‐Thelengthoftimeaftermainflamelightoffthatisrequireduntilanaccurate,
representativeO
2
valueisreadbytheO
2
sensor.Basically,thetimeittakestoreplacealloftheairin
theboilerwithproductsofcombustion.Thisparameterisamultiplierthatistakentimesthedelaytime
atlowfire(TauLowFire)todeterminethelengthofwaitingtimebeforearepresentativeO
2
valueis
measuredandtheO
2
trimcanengage.
IfTauLowFirewasreadtobe5secondsduringO
2
ControlCurvecommissioning,and
NumberTauSuspendissetto10,thentheO
2
trimwouldengage50secondsaftermainflamelightoff.
Asettingof10willworkforalmostallapplications,andwillbeconservativeformost.Highernumbers
(morewaitingtime)aremoreconservativeandlowernumbersarelessconservative.
Menupath:Params&Display>O2Contr/Alarm>GasSettings>Startmode
Startmode‐ThisdetermineshowtheburnertransitionsfromlightofftoengagingtheO
2
trim.Twoof
themodes,“IgnLoadTC”and“IgnPtWithTC”,requireacombustionairtemperaturesensor.
Immediatelyaftermainflamelightoff,theO
2
sensordoesnothaveavalidreadingsincethegaspathof
theboilerisfullofair.Someburnerdesigns,mostnotablyultralowNOxmeshburners,requiresome
typeofcompensationatlightofftoensureflamestabilitybeforetheO
2
sensorhasavalidreading.Four
optionsareavailable:
1. Standard‐Burnerwillmodulaterightafterlightoff,notwaitingfortheO
2
trimtoengage.O
2
trim
willengageafterthetimedefinedbyNumberTauSuspendexpiresattheburner’scurrentload.
2. IgnLoadTC‐Thiswillvarytheignitionpositions(specialpositions)oftheactuatorsbasedonthe
combustionairtemperatureandalsobasedonadefinedloadnumber(parameterLoadofIgnition).
Thisalsowilldrivethe"temperaturecompensated"actuatorstoPoint2(orwhicheverpointis
definedbypa
rameterStartPointOp).TheburnerwillbeheldinPhase60atPoint2(orwhichever
pointisdefinedbyparameterStartPointOp)untilthetimedefinedbyNumberTauSuspendexpires.
TheburnerwillthenbereleasedtomodulatewiththeO
2
trimactive.
3. IgnPtWithTC‐Thiswillnotvarytheignitionpositions(specialpositions)oftheactuatorsbasedon
thecombustionairtemperature.Itwilldrivetheactuatorsfromthetemperaturecompensatedset
ignitionpositionstoPoint2(orwhicheverpointisdefinedbyparameterStartPointOp).Theburner
willbeheldinPhase60atPoint2(orwhicheverpointisdefinedbyparameterStartPointOp)unt
il
thetimedefinedbyNumberTauSuspendexpires.Theburnerwillthenbereleasedtomodulatewith
theO
2
trimactive.
4. IgnPtWoutTC‐Similarto“IgnPtWithTC”,butlessaccuracyduetothelackofacombustionair
sensor.
Onburnerswithawideflamestabilityb and,suchastraditionalnozzlemixingburners withlittleorno
FGR,aStartModesettingof“standard”typicallyworkswell.Onburnerswithamorenarrowflame
stabilityband(lowandultralowNOxmeshburners),“IgnPtWithTC”typicallyworkswell.
Menupath:Params&Display>O2Contr/Alarm>GasSettings>Startmode
HOME

Table of Contents

Other manuals for Siemens LMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV5 Series and is the answer not in the manual?

Siemens LMV5 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV5 Series
CategoryControl Systems
LanguageEnglish

Related product manuals