Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
139
PULSE LENGTH The field is available with the action "ENERGY PULSE".
Pulse length.
Range: 30 to 500 ms
Default: 100 ms
The minimum length of the pulse pause corresponds to the pulse
duration specified.
DIGITAL INPUT
Figure 9-11 "DIGITAL INPUT" device setting
ACTION Method of using the digital input:
NONE: The digital input is switched off.
PULSE INPUT: Counting of input pulses.
Note: The universal counter must also be
parameterized for pulse counting. In the
"ADVANCED > UNIVERSAL COUNTER"
device setting, set the field "SOURCE" to
the value "DIG. INPUT".
ON/OFF-PEAK: Switching between tariffs. Off-peak if input
active.
DEMAND SYNC: Synchronization of power demand.
Default: NONE
PULSES PER
UNIT
The field is available with the action "PULSE INPUT".
Range: 1 to 999
Default: 1
Figure 9-12 "DIGITAL INPUT" device setting
UNIT Visible with action "PULSE INPUT"
Countable unit with pulse counting:
kWh (active energy)
kvarh (reactive energy)