Accessories
9.17 Motor operator
Manual, 08/2017, L1V30368969104A-02
171
Replacing the motor operator of the 3KC4 transfer switching equipment
WARNING
Danger! High voltage
Turn off and lock out all power supplying this device before working on this device.
Installation and maintenance work on this device must be carried out by authorized persons
with the appropriate electrical training only.
The following steps describe the replacement of the motor operator on the 3KC4 transfer
switching equipment.
1. Switch the transfer switching equipment from "Auto" mode to "Manual" mode.
Figure 9-35 Set the switch to the "Manual" position
2. Switch the transfer switching equipment to position 0 (OFF).
3. Press the button on the cover cap.
Figure 9-36 Disassembling the cover cap and the power supply kit
4. Slide the cover cap carefully backwards and remove it.
5. Remove the power supply of the transfer switching equipment (pin 301 and 302).
6. Remove the control inputs (pins 312-317).
Figure 9-37 Removing control inputs
7. Remove the outputs (pins 63, 64, 24, 14, 04, 13).