Table 13-5 Settings for Logon Configurations
Parameter Default Setting Setting Range
Logon activation yes To disable the logon function, select no
To enable the logon function, select yes
Logon password 000000 Any, 6 to 14 characters
Session timeout (min) 10 min 0 min (no timeout) to 1440 min (1 day)
If 0 is selected, after the device starts up, you only
have to log on once.
Date and Time
Table 13-6 Settings for Time Synchronization
Parameter Default Setting Setting Range
Source time synchronization Internal Internal
Ethernet NTP
Fieldbus
Time zone offset to UTC +00:00 -12:00 to +13:00 (hours)
(in increments of 0.5 h)
Daylight Saving Time switch-
over
Yes No
Yes
DST offset +01:00 0:00 to +2:00 (hours)
(in increments of 0.5 h)
Start of DST March
Last week
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday
2:00 AM
Sunday to Saturday
12:00 AM to 11:00 PM
(in increments of 1 h)
End of DST October
Last week
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday
3:00 AM
Sunday to Saturday
12:00 AM to 11:00 PM
(in increments of 1 h)
Additional Parameters if the Source is Ethernet NTP (Communication Ethernet bus protocol is set to
Modbus TCP or IEC 61850)
Primary NTP server IP Address 0.0.0.0 Any
No polling of the NTP server if 0.0.0.0 is entered
Secondary NTP server IP
Address
0.0.0.0 Any
No polling of the NTP server if 0.0.0.0 is entered
Error indication after 10 min 2 min to 120 min
13.2.2
Operational Indications and Operating Parameters
13.2 Basic Functions
264 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022