Technical specifications
9.4 Fail-safe mode
KP8, KP8F, KP32F
Operating Instructions, 11/2011, A5E03284305-02
111
Power supply
Parameter Value Comment
Hardware Fault Tolerance 0
Classification A
Architecture 1oo1D
Failure mode
Detected
Undetected
Dangerous process value
22.50 FIT
0.22 FIT
Due to failures in the power supply
Failure Mode Diagnostic
Detected
Undetected
No error signaling or no safe
values
0 FIT
0 FIT
Calculation according
IEC 13849-1, CAT4
Diagnostic Coverage 99.03 %
Diagnostic test interval < 10 ms Voltage monitoring in hardware
Safe Failure Fraction 99.84 %
Fail-safe mode for 1oo1 evaluation
According to IEC 61508
Systematic Capability SIL3
Mode of operation High and low demand mode
Meantime to Restoration (MTTR) 100 h
Probability of a dangerous failure per hour
(PFH)
5.95 × 10
–10
1/h
Probability of a dangerous failure on demand
(PFD)
2.61 × 10
–5
Safe Failure Fraction (SFF) 99.19 %
Diagnostic test interval 15 ms
Proof Test Interval 10 y
Lifetime 10 y
According to IEC 13849-1
Meantime to Failure (MTTF
d
) 560 y
Meantime to Restoration (MTTR) 100 h
Diagnostic Coverage (DC
avg
) 98.90 %
Performance Level d
Category 3
According to EN 954-1
Category 3