Assigning parameters for the HMI device in STEP 7   
6.3 KP8 and KP8F 
  KP8, KP8F, KP32F 
76  Operating Instructions, 11/2011, A5E03284305-02 
6.3.3  Setting the properties of the digital inputs/outputs 
Requirement 
●  A project is open in "HW Config". 
Procedure    
1.  Double click in the properties window on slot 1. 
The "Properties – KP8 inputs/outputs" dialog box opens. 
2.  Open the "Addresses" tab. 
In the "Inputs" and "Outputs" groups, the start values of the address areas are set 
depending on the controller used. 
 
Parameter  Meaning 
Inputs > Start  Start of address range in which the PROFIsafe inputs/outputs for 
the fail-safe HMI device are mapped. 
Inputs > Process Image  Process image to which the address range belongs. 
This parameter cannot be set with controllers of the 
SIMATIC CPU 300 type. 
Outputs > Start  Start of address range in which the PROFIsafe inputs/outputs for 
the fail-safe HMI device are mapped. 
Outputs > Process Image  Process image to which the address range belongs. 
This parameter cannot be set with controllers of the 
SIMATIC CPU 300 type. 
3.  Change the entries, if required. 
4.  Select the "Parameters" tab. 
5.  Open the "Parameters > Device-specific parameters" folder. 
 
Parameter  Meaning 
Duration of the light test  The value range from 0 to 60 s can be set. 
With the value "0", no light test is executed. 
Default setting is 5 s. 
Brightness  Adjustable: 
very bright, bright, normal, dark or very dark 
Default setting is "normal". 
Function of the clamp 0  Adjustable: 
Input or output, default setting is input 
Function of the clamp 1  Adjustable: 
Input or output, default setting is input 
…  … 
Function of the clamp 6   Adjustable: 
Input or output, default setting is output 
Function of the clamp 7  Adjustable: 
Input or output, default setting is output