EasyManua.ls Logo

Siemens SIMATIC KP8 - Connecting KP32 F - Fail-Safe Inputs; General; Connecting the EMERGENCY STOP Button

Siemens SIMATIC KP8
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and connecting the HMI device
4.4 Connecting the HMI device
KP8, KP8F, KP32F
58 Operating Instructions, 11/2011, A5E03284305-02
4.4.7 Connecting KP32F - fail-safe inputs
4.4.7.1 General
The KP32F is intended for the connection of EMERGENGY STOP buttons and fail-safe
sensors. Please observe the information in Section "Sensor for 1oo1 mode (Page 42)" and
"Sensor for 1oo2 mode (Page 43)".
Note
For supplying the fail-safe inputs, only inputs labeled with VS may be used on the HMI
device.
Only connect fail-safe inputs if these are also used. This also applies for disabled fail-safe
inputs.
Follow the notes about connectors in section"Connecting the power supply (Page 52)".
4.4.7.2 Connecting the EMERGENCY STOP button
Requirement
1 connector, see accessory kit
1 or 2 EMERGENCY STOP buttons
Note
If you selected the option "No evaluation" for the KP32F in the "Evaluation of the sensor"
parameter in STEP 7 HW Config and no sensor is connected, the value 0 will be reported
to the controller for the sensor values in the process image.
See section "KP32F - Bit assignment in the process image (Page 119)".

Table of Contents

Related product manuals