Assigning parameters for the HMI device in STEP 7
6.3 KP8 and KP8F
KP8, KP8F, KP32F
Operating Instructions, 11/2011, A5E03284305-02
83
Procedure
1. Perform steps 1 to 9 as described in section "KP8F – Configure Shared Device
(Page 80)".
2. Select the "Access" tab.
The followi
ng
dialog appears:
3. Select "" for the Shared Device connection.
The parameter indicates that there is no access by the controller.
4. Click "OK".
The entry is saved. The dialog box closes.
Result
Shared Device is configured for the KP8F and for a non fail-safe controller.