Assigning parameters for the HMI device in STEP 7
6.5 Setting the PROFIsafe address
KP8, KP8F, KP32F
Operating Instructions, 11/2011, A5E03284305-02
93
Example
In the HW Config of the STEP 7 project, set the binary address for "383" as the PROFIsafe-
target address:
Corresponding setting on the DIP switch: 0101111111
● 1 = switch setting "ON"
● 0 = switch setting "OFF".
Set the DIP switch on the back of the KP8F or the KP32F as follows:
6ZLWFK $GGUHVV:HLJKWLQJ%LWQXPEHU
2)) 21
The illustrated switch settings correspond with the binary address 383.
Result
The HMI device can be uniquely identified by the configured PROFIsafe target address.