Programming Instructions
R
02/92
9.2.4 Parameter Assignment
BGDB
:
KY
= X, y
x =
Module address (BG)
128< X
<248
for P/Q :
KS=P
0
<
X
<248
for P/Q: KS=Q
x = Data block number
(DB)
1< y
<255
2< y
<255
for
S5–
155U and
S5–
135U
(Specif~ation
of a DX data block is not possible)
P/Q
: KS = P
Normal
1/0
area
KS = Q
Extended 1/0 area
PAFE :
In case of illegal parameterization the signal status is”1”. The recognized error is
then shown by the assignment of the flag byte
FY
255:
F 255.0
F 255.1
F 255.2
F 255.3
F 255.4
F 255.5
F 255.6
F 255.7
The module address is outside of the specified area or not within the
8–bit grid pattern (first part of parameter
BGDB).
The
parameter
P/Q is not set with ‘P-’ or
‘Q–’
(not for programmable controller S5-115U)
The specified user data block number is zero or one.
(one only for
S5-155U
andS5-115U)
(second part of parameter
BGDB)
The specified user data block does not exist or is too short.
(second part of parameter
BGDB)
QVZ, no module found under this address.
(first part of parameter
BGDB)
(only for
S5-155U
and
S5-135U)
When the “verify–read
(PR)”
or “calculate average value (MB)”
special function is enabled, the “number” parameter is located
(outside the permissible area from O to 15) in data word
DR
182 or
DR
184 of the user data block.
—
SPFE :
Is set, if after an access the SP bit is not reset by the module within a specified
time interval.
9–4
1P
241 Equipment Manual
@
sif3MWIS
AG 1989, Order No.: 6ES5 998-0KD21