041 The firmware does not support the option module.
Suppl. info: \%u
Cause Supplementary info = 1:
An option module is inserted (P0872) or parameterized (P0875), which
is not supported by the firmware release of the control module.
Remedy Supplementary info = 1:
– Upgrade the firmware
– Use a legal option module
– Cancel the option module with P0875 = 0
Supplementary info = 2:
– Use a permissible option module (DP3)
– Cancel the option module with P0875 = 0
Supplementary info = 3:
– Replace the option module hardware DP1 by option module DP2 or
DP3, without changing the drive parameters and the master
configuring. The parameter for the expected option module remains
at P0875 = 2.
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
042 Internal software error. Supplementary info \%u
Cause There is an internal software error.
Supplementary information: only for siemens-internal error diagnostics
Remedy – Execute POWER ON-RESET (press button R)
– Re-load the software into the memory module (execute software up-
date)
– Contact the Hotline
– Replace control module
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
043 Firmware, option module
Cause The option module does not contain the currently required firmware.
Remedy Use a module with suitable firmware or upgrade the firmware
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
044 Connection to the option module failed. Supplemen-
tary info \%X
Cause The BUS coupling has failed.
Remedy – Execute POWER ON-RESET (press button R)
– Replace option module
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
7 Fault Handling/Diagnostics