7.3 List of faults and warnings
7-637
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
045 Expected option module is axially unequal
Cause The option module type, expected from the parameterization, is differ-
ent for the two axes of a two-axis module.
Remedy Set the expected option module type in P0875 the same for both axes,
or cancel for axis B by setting P0875 to 0.
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
048 Illegal status PROFIBUS hardware
Cause An illegal status of the PROFIBUS controller was recognized.
Remedy – Execute POWER-ON RESET
– Check the PROFIBUS unit screw connection
– Replace drive module
Acknowledgement POWER ON
Stop response STOP II
101 Target position block \%n < plus software limit switch
Cause The target position specified in this block lies outside the range limited
by P0316 (plus software limit switch).
Remedy – Change the target position in the block
– Set the software limit switches differently
Acknowledgement RESET FAULT MEMORY
Stop response STOP VI
102 Target position block \%n < minus software limit
switch
Cause The target position specified in this block lies outside the range limited
by P0315 (minus software limit switch).
Remedy – Change the target position in the block
– Set the software limit switches differently
Acknowledgement RESET FAULT MEMORY
Stop response STOP VI
103 Block number \%n: Direct output function not possible
Cause For the SET_O or RESET_O command, an illegal value was entered in
P0086:64 (command parameter).
Remedy Enter value 1, 2 or 3 in P0086:64 (command parameter).
Acknowledgement RESET FAULT MEMORY
Stop response STOP V