Electrical installation
4.9 Signal connections
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
101
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must b
e connected.
This is achieved through one of the following measures:
Also route the reference ground of the digital inputs.
A jumper to terminal M. (
This removes the electrical isolation for these digital
inputs.)
Note
If the 24 V supply is brief
ly interrupted, then the digital outputs are deactivated during this
X126: PROFIBUS connection
The PROFIBUS is connected by means of a 9-pin SUB D socket (X126). The connections
are electrically isolated.
Table 4- 12 PROFIBUS interface X126
Power supply for teleservice, ground
Receive/transmit data P (B)
PROFIBUS data reference potential
Power supply for teleservice, + (24 V)
Receive/transmit data N (A)
A teleservice adapter can be connected to the PROFIBUS interface for remote diagnostics.
The power supply for the teleservice (terminals 2 and 7) can have a load of up to 150 mA.