Technical specifications
12.3 Technical data
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
653
Cabinet devices version A, 660 V - 690 V 3 AC
Table 12- 7 Version A, 660 ... 690 V 3 AC, Part 1
- for I
L
at 50 Hz 690 V
1)
H
1)
kW
1750
1950
2150
- Rated current I
N
- Base load current I
L
2)
3)
A
A
1729
1720
1948
1940
2158
2150
- Rated input current
4)
- Input current, max.
- Current requirements for 24 V DC
A
A
A
1800
2765
4.7
2030
3115
4.7
2245
3450
4.7
- Line voltage
- Line frequency
- Electronic power supply
V
ACrms
Hz
660 V 3 AC -10 % to 690 V 3 AC +10 % (-15 % < 1 min)
47 ... 63
3
pA
dB(A) 75/78 75/78 75/78
- Recommended: IEC
4)
- maximum: IEC
mm
2
mm
2
Per sub-cabinet:
4 x 150
8 x 240
Per sub-cabinet:
4 x 150
8 x 240
Per sub-cabinet:
4 x 150
8 x 240
- Recommended: IEC
5)
- maximum: IEC
mm
2
mm
2
Per sub-cabinet:
3 x 185
6 x 240
Per sub-cabinet:
3 x 185
6 x 240
Per sub-cabinet:
3 x 185
6 x 240
Protective conductor connection
Per sub-cabinet:
Per sub-cabinet:
Per sub-cabinet:
(standard version)
- Width
- Height
mm
mm
3600
2000
3600
2000
3600
2000
Basic Line Module frame size
Weight (without options), approx.