Technical specifications
12.3 Technical data
Converter cabinet units
654 Operating Instructions, 07/2016, A5E03347396A
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor
protection
(without option L26)
Rated current
A
A
Per sub-cabinet:
3NA3365-6
2 x 500
3
Per sub-cabinet:
3NE1435-2
2 x 560
Per sub-cabinet:
3NA3362-6
3 x 425
3
Per sub-cabinet:
3NE1436-3
2 x 630
Per sub-cabinet:
3NA3365-6
3 x 500
3
Per sub-cabinet:
3NE1334-2
3 x 500
Short-circuit current rating per IEC
6)
kA 2 x 85 2 x 85 2 x 85
Minimum short-circuit current
7)
Rated output of a typical 6-pole standard induction motor based on I
L
or I
H
at 690 V 3 AC 50 Hz.
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
The base-load current I
H
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
The current values given here are based on the rated output current.
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
(National Electrical Code) or CEC (Canadian Electrical Code) standards.
In conjunction with the specified fuses or circuit breakers.
7)
Minimum current required for reliably triggering protective devices.