Operation
6.4 Command sources
Converter cabinet units
282 Operating Instructions, 07/2016, A5E03347396A
"PROFIdrive NAMUR" default setting
Preconditions
The NAMUR terminal block (option B00) is installed in the cabinet unit.
The "PROFIdrive" default setting was chosen during commissioning:
STARTER (p0700):
AOP30 (p0700):
Figure 6-15 Command sources - AOP30 <-> PROFIdrive NAMUR
The priority of the command sources is shown in the diagram "Command sources -
AOP30 <-> PROFIdrive NAMUR".
Note
Emergency OFF signals
The emergency OFF and motor protection signals are always active (regardless of the
command source).
All of the supplementary setpoints are deactivated for LOCAL master control.