Setpoint channel and closed-loop control
7.3 V/f control
Converter cabinet units
434 Operating Instructions, 07/2016, A5E03347396A
Parameter
•
r0056.5
Voltage boost at startup active/inactive
•
r0056.6
Acceleration voltage active/inactive
•
p0304
Rated motor voltage
•
p0305
Rated motor current
•
r0395
Stator resistance, actual
•
p1310
Starting current (voltage boost) permanent
•
p1311
Starting current (voltage boost) when accelerating
•
p1312
Startin
g current (voltage boost) when starting
•
r1315
Voltage boost total
7.3.2
Resonance damping
Description
Resonance damping damps oscillations in the active current, which often occur during no-
load operation.
The resonance damping is active in a range from approximately 6% of the rated motor
frequency (p0310). The switch-off frequency is determined by p1349.
For p1300 = 5 and 6 (textiles) the resonance damping is internally disabled in order to be
able to precisely set the output frequency.
Figure 7-9 Resonance damping