Setpoint channel and closed-loop control
7.3 V/f control
Converter cabinet units
434 Operating Instructions, 07/2016, A5E03347396A
r0056.5
Voltage boost at startup active/inactive
r0056.6
Acceleration voltage active/inactive
p0304
p0305
r0395
Stator resistance, actual
p1310
Starting current (voltage boost) permanent
p1311
Starting current (voltage boost) when accelerating
p1312
g current (voltage boost) when starting
r1315
Resonance damping
Description
Resonance damping damps oscillations in the active current, which often occur during no-
load operation.
The resonance damping is active in a range from approximately 6% of the rated motor
frequency (p0310). The switch-off frequency is determined by p1349.
For p1300 = 5 and 6 (textiles) the resonance damping is internally disabled in order to be
able to precisely set the output frequency.
Figure 7-9 Resonance damping