Operation
6.4 Command sources
Converter cabinet units
280 Operating Instructions, 07/2016, A5E03347396A
6.4.3
"NAMUR" default setting
Preconditions
The NAMUR terminal block (option B00) is installed in the cabinet unit.
The "NAMUR" default setting was chosen during commissioning:
•
STARTER (p0700):
"NAMUR"
•
AOP30 (p0700):
"7: NAMUR"
Command sources
Figure 6-13 Command sources - AOP30 <-> NAMUR terminal block
Priority
The priority of the command sources is shown in the diagram "Command sources -
AOP30 <-> NAMUR terminal block".
Note
Emergency OFF signals
The emergency OFF and motor protection signals are always active (regardless of the
command source).
All of the supplementary setpoints are deactivated f
or LOCAL master control.