Operation
6.5 Setpoint sources
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
287
Signal flow diagram
Figure 6-18 Signal flow diagram: Motorized potentiometer
Function diagram
FP 3020
Motorized potentiometer
Parameter
•
p1030
Motorized potentiometer, configuration
•
p1037
Motorized potentiometer, maximum speed
•
p1038
Motorized potentiometer, minimum
speed
•
p1047
Motorized potentiometer, ramp
-up time
•
p1048
Motorized potentiometer, ramp
-down time
•
r1050
Motorized potentiometer, setpoint after the ramp
-function generator
6.5.3
Fixed speed setpoints
Description
A total of 15 variable fixed speed setpoints are available.
The default setting specified for the setpoint sources during commissioning via STARTER or
the operating panel makes three fixed speed setpoints available. They can be selected via
terminals or fieldbus.