Operation
6.5 Setpoint sources
Converter cabinet units
288 Operating Instructions, 07/2016, A5E03347396A
Precondition
The default setting for the fixed speed setpoints was chosen during commissioning:
•
STARTER (p1000):
"Fixed setpoint"
•
AOP30 (p1000):
"4: Fixed setpoint"
Signal flow diagram
Figure 6-19 Signal flow diagram: Fixed speed setpoints
Function diagram
FP 3010
Fixed speed setpoints
Parameter
•
p1001
Fixed speed setpoint 01
•
p1002
Fixed speed setpoint 02
•
p1003
Fixed speed setpoint 03
•
r1024
Fixed speed setpoint effective
Note
Other fixed speed setpoints are available using p1004 to p1015. They can
be selected using
p1020 to p1023.