Operation
6.4 Command sources
Converter cabinet units
278 Operating Instructions, 07/2016, A5E03347396A
6.4.2
"TM31 terminals" default setting
Preconditions
The customer Terminal Module option (G60) is installed in the cabinet unit.
The "TM31 Terminals" default setting was chosen during commissioning:
•
STARTER (p0700):
"TM31 Terminals"
•
AOP30 (p0700):
"6: TM31 terminals
Command sources
Figure 6-11 Command sources - AOP30 <-> TM31 terminals
Priority
The priority of the command sources is shown in the diagram "Command sources -
AOP30 <-> TM31 terminals".
Note
Emergency OFF signals
The emergency OFF and motor
protection signals are always active (regardless of the
command source).
All of the supplementary setpoints are deactivated for LOCAL master control.