Functions, monitoring, and protective functions
9.2 Drive functions
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
525
Synchronization
Description
The "Synchronization" function and an existing VSM10 Voltage Sensing Module (to measure
the line voltage) synchronizes a motor to the line supply. The connection to the line supply or
the required contactor activation can be made via the available bypass function or via a
higher-level control system.
The use of the bypass function permits the temporary (e.g. to perform maintenance work
without system standstill) or permanent operation of the motor on the line supply.
The p3800 parameter activates the synchronization. The voltage is acquired via a VSM10
assigned to the drive (via DRIVE-CLiQ) and measures the line supply voltage.
● Connector inputs for the actual voltage sensing of the motor via VSM10 (p3661, r3662)
● Setting a phase difference (p3809)
● Can be activated by parameter (p3800)
● Enable via parameter (p3802)
Technology functions - Synchronizing
p3800[0...n]
Sync network drive activation
p3801[0...n]
-line-drive drive object number
p3802[0...n]
network drive enable
r3803
CO/BO: Sync network drive control word
r3804
CO: Sync network drive target frequency
r3805
CO: Sync network drive frequency difference
p3806[0...n]
Sync network drive frequency difference threshold value
r3808
ork drive phase difference
p3809[0...n]
Sync network drive phase setpoint value
p3811[0...n]
Sync network drive frequency limitation
r3812
CO: Sync network drive correction frequency