Functions, monitoring, and protective functions
9.2 Drive functions
Converter cabinet units
524 Operating Instructions, 07/2016, A5E03347396A
Notes on setting the release (opening) time (p1216):
The release time (p1216) should be set longer than the actual release time of the holding
brake. As a result, the drive will not accelerate when the brake is closed.
Notes on setting the closing time (p1217):
The closing time (p1217) should be set longer than the actual closing time of the holding
brake. As a result, the pulses are suppressed only after the holding brake is closed.
If the closing time (p1217) is set too low compared to the actual closing time of the
holding brake, the load may drop suddenly.
If the closing time (p1217) is set too high compared to the actual closing time of the
holding brake, the controller acts against the holding brake and thus reduces its service
life.
Function diagram
FP 2701
Simple brake control (r0108.14 = 0)
Parameter
r0056.4
Magnetizing completed
r0060
CO: Speed setpoint before the setpoint filter
r0063[0...2]
CO: Actual speed value
r0108.14
Extended brake control
p0855[C]
BI: Unconditionally relea
se holding brake
p0856
BI: Speed controller enabled
p0858
BI: Unconditionally apply holding brake
r0899.12
BO: Holding brake open
r0899.13
BO: Command, close holding brake
p1215
Motor holding brake configuration
p1216
Motor holding brake release time
p1217
Motor holding brake closing time
p1226
Threshold for standstill detection
p1227
Standstill detection monitoring time
p1228
Pulse suppression delay time
p1278
Brake control diagnostic evaluation