Technical specifications
12.2 General data
Converter cabinet units
650 Operating Instructions, 07/2016, A5E03347396A
Current derating as a function of the pulse frequency
When the pulse frequency is increased, the derating factor of the output current must be
taken into account. This derating factor must be applied to the currents specified in the
technical data for the cabinet units.
Table 12- 6 Derating factor of the output current as a function of the pulse frequency
Output current
at 1.25 kHz
Derating factor at the pulse frequency
Supply voltage 3 AC 660 ... 690 V
Note
Derating factors for pulse frequencies in the range between fixed values
For pulse frequencies in the range between the specified fixed values, the relevant derating
factors can be determined by linear interpolation.