Operation
6.6 Control via the operator panel
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
295
Menu commissioning / service
6.6.5.1
This option enables you to re-commission the drive from the main menu.
Only the basic commissioning parameters are queried and stored permanently.
Complete commissioning with motor and encoder data entry is carried out. Following this,
key motor parameters are recalculated from the motor data. The parameter values
calculated during previous commissioning are lost.
In a subsequent motor identification procedure, the calculated values are overwritten.
The selection screen for motor identification appears.
The actual operating hours of the fan in the power unit is displayed.
After a fan replacement, the operating hours counter for monitoring the fan operating time
must be reset.
Device commissioning
Device commissioning
In this menu, you can enter the device commissioning status directly. This is the only way
that you can reset parameters to the factory setting for example.