EasyManua.ls Logo

Siemens SINAMICS G150 - Lock AOP LOCAL Mode

Siemens SINAMICS G150
680 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
6.6 Control via the operator panel
Converter cabinet units
310 Operating Instructions, 07/2016, A5E03347396A
6.6.7.7
Lock AOP LOCAL mode
Settings: MENU Commissioning/Service AOP settings Control settings
Save AOP local mode
(factory setting: no)
Yes
: Deactivates the "Control via operator panel" function, thereby disabling the
LOCAL/REMOTE key.
No
: Activates the LOCAL/REMOTE key.
Note
Lock LOCAL
LOCAL functionality can also be inhibited on the drive by means of the p0806 parameter (BI:
Inhibit master control).
6.6.7.8
Acknowledge error from the AOP
Settings: MENU Commissioning/Service AOP SettingsControl Settings
Acknowledge error from the AOP
(factory setting: yes)
Yes
: Errors can be acknowledged via the AOP.
No
: Errors cannot be acknowledged via the AOP.
6.6.7.9
CDS setting via AOP
Settings: MENU Commissioning/Service AOP settings Control settings
CDS changeover via AOP
(factory setting: No)
Yes
: In the LOCAL mode, in the operating screen form the active CDS can the changed
by one. This is helpful, if operation via an AOP would not be possible due to the fact that
a standard telegram is active.
When CDS0 or 2 is active, "CDS+1" switches to CDS1 or CDS3.
When CDS1 or 3 is active, "CDS-1" switches to CDS0 or CDS2.
No
: In the LOCAL mode, in the operating screen form the active CDS cannot be changed
by one.