Technical specifications
12.3 Technical data
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
655
Table 12- 8 Version A, 660 ... 690 V 3 AC, Part 2
- for I
L
at 50 Hz 690 V
1)
H
1)
kW
2400
2700
- Rated current I
N
- Base load current I
L
2)
3)
A
A
2413
2390
2752
2685
- Rated input current
4)
- Input current, max.
- Current requirements for 24 V DC
A
A
A
2510
3860
4.7
2865
4400
6.0
- Line voltage
- Line frequency
- Electronic power supply
V
ACrms
Hz
660 V 3 AC -10 % to 690 V 3 AC +10 % (-15 % < 1 min)
47 ... 63
3
pA
dB(A) 75/78 75/78
- Recommended: IEC
4)
- maximum: IEC
mm
2
mm
2
Per sub-cabinet:
4 x 150
8 x 240
Per sub-cabinet:
4 x 150
8 x 240
- Recommended: IEC
5)
- maximum: IEC
mm
2
mm
2
Per sub-cabinet:
3 x 185
6 x 240
Per sub-cabinet:
3 x 185
6 x 240
Protective conductor connection
Per sub-cabinet:
Per sub-cabinet:
(standard version)
- Width
- Height
mm
mm
3600
2000
4400
2000
Basic Line Module frame size
Weight (without options), approx.
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor protection
(without option L26)
Rated current
A
A
Per sub-cabinet:
3NA3365-6
3 x 500
3
Per sub-cabinet:
3NE1334-2
3 x 500
Per sub-cabinet:
3NA3372
3 x 630
3
Per sub-cabinet:
3NE1436-3
3 x 630