Electrical installation
4.9 Signal connections
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
105
Note
The LAN (Ethernet) interface does not support Auto MDI(X)
. For this reason, only crossover
cables may be used to connect devices.
For diagnostic purposes, the X127 LAN interface features a green and a yellow LED. These
LEDs indicate the following status information:
Table 4- 15 LED statuses for the X127 LAN interface
Link port
10 or 100 Mbit link available
Activity port
X140: serial interface (RS232)
The AOP30 operator panel for operating/parameterizing the device can be connected via the
serial interface. The interface is located on the underside of the Control Unit.
Table 4- 16 Serial interface (RS232) X140
5 Ground Ground reference
Connector type: 9-pin SUB D connector
Note
Connecting cable to the AOP30
The connection cable to AOP30 may only contain the three contacts which are shown in the
drawing; a complete
ly allocated cable may not be used.