Electrical installation
4.9 Signal connections
Converter cabinet units
112 Operating Instructions, 07/2016, A5E03347396A
Table 4- 18 Terminal block X520
: - 3 … +30 V
typical: 10 mA at 24 V DC
:
for "0" to "1": Typ. 50 µs max. 100 µs
for "1" to "0": Typ. 130 µs, max. 150 µs
:
Reference potential is terminal M1
(including ripple)
High level: 15 … 30 V
2 DI 1
6 M
Max. connectable cross-section: 1.5 mm²
1)
DI: digital input; M1: ground reference; M: Electronics ground
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
Terminal M1 must be connected so that the digital inputs (DI) can function.
This is achieved through one of the followi
ng measures:
Also route the reference ground of the digital inputs.
A jumper to terminal M. (
This removes the electrical isolation for these digital
inputs.)