Electrical installation
4.10 Other connections
Converter cabinet units
122 Operating Instructions, 07/2016, A5E03347396A
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning using parameter p0230 = 2.
Damage to the dv/dt filter if a motor is not connected
dv/dt filters which are operated without a motor being connected can be damaged or
destroyed.
• Never operate a dv/dt filter connected to the Power Module without a connected motor.
Note
Setting pulse frequencies
It is permissible to set pulse frequencies in the range between the rated pulse frequency and
the maximum pulse frequency when a
dv/dt
filter plus Voltage Peak Limiter is used. When so
doing, take into account the "Current d
erating as a function of the pulse frequency; see
During commissioning, the dv/dt filter plus Voltage Peak Limiter must be logged on using
STARTER or the AOP30 operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.