Electrical installation
4.10 Other connections
Converter cabinet units
130 Operating Instructions, 07/2016, A5E03347396A
Reconnection to the 24 V DC Button Circuit
When using the 24 V DC pushbutton circuit, you must remove the following jumpers at
terminal block -X120:
4-5, 9-10, and 11-14
You must also insert the following jumpers at terminal block -X120:
4-11, 5-10, and 9-14
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs on -K120) are
described in the "Additional Operating Instructions" of the Operating Instructions.