Electrical installation
4.10 Other connections
Converter cabinet units
162 Operating Instructions, 07/2016, A5E03347396A
Note
Operation of unipolar HTL encoders
When unipolar HTL encoders are used, A*, B*, and R* on the terminal block must be
jumpered with M_Encoder (X531).
Table 4- 55 Encoder connection X531
Terminal
Signal name
Technical data
1
P encoder 5 V/24 V
Encoder supply
2
M encoder
Ground for encoder power supply
3 -Temp
1)
Temperature sensor KTY84-1C130 /
PT1000 / PTC
4 +Temp
1)
Temperature sensor KTY84-1C130 /
PT1000 / PTC
5
Reserved, do not use
6
Reserved, do not use
7
Reserved, do not use
8
Reserved, do not use
Max. connectable cross-section: 1.5 mm²
Measuring current via temperature sensor connection: 2 mA
1)
Accuracy of the temperature measurement:
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
WARNING
Danger to life due to electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Only use temperature sensors that fully comply with the specifications of the safety
isolation.