Loading...
Electrical installation
4.10 Other connections
Converter cabinet units
182 Operating Instructions, 07/2016, A5E03347396A
X100 to X103: DRIVE-CLiQ interface
Table 4- 61 DRIVE-CLiQ interface X100 – X103
Pin
Signal name
Technical data
1
TXP
Transmit data +
2 TXN Transmit data -
3
RXP
Receive data +
4
Reserved, do not use
5
Reserved, do not use
6
RXN
Receive data -
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
Power supply
B
M (0 V)
Electronics ground
Connector type: RJ45 socket
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0