Electrical installation
4.10 Other connections
Converter cabinet units
186 Operating Instructions, 07/2016, A5E03347396A
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must b
e connected.
This is achieved through one of the following measures:
1.
Also route the reference ground of the digital inputs.
2.
A jumper to terminal M. (
Note:
This removes the electrical isolation for these digital
inputs.)
Note
If the 24 V supply is brief
ly interrupted, then the digital outputs are deactivated during this
time.
X127: LAN (Ethernet)
Table 4- 64 X127 LAN (Ethernet)
Pin
Designation
Technical data
1
TXP
Ethernet transmit data +
2
TXN
Ethernet transmit data -
3
RXP
Ethernet receive data +
4
Reserved, do not use
5
Reserved, do not use
6
RXN
Ethernet receive data -
7
Reserved, do not use
8
Reserved, do not use
Connector type: RJ45 socket
Note
The LAN (Ethernet) interface does not support Auto MDI(X). For this reason, only crossover
cables may be used to connect dev
ices.