Commissioning
5.3 Procedure for commissioning with STARTER
Converter cabinet units
208 Operating Instructions, 07/2016, A5E03347396A
Configuring the drive unit
Figure 5-13 Configuring the drive unit
⇒
Under
Connection voltage
, choose the correct voltage. Under
Cooling method:
choose the
correct cooling method for your drive unit.
⇒
Under
Standard:
, choose "IEC" to restrict the selection of drive units offered.
Note
Make a pre-selection
In this step
, you make a preliminary selection of the cabinet units. You do not define the line
voltage and cooling method yet.
⇒
A list is now displayed under
Drive unit selection:
. Choose the corresponding drive unit
according to type (article no.) (see rating plate).
⇒
Click
Continue >