Operation
6.5 Setpoint sources
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
285
Parameter
•
r4052
Actual input voltage/current
•
p4053
Analog inputs smoothing time constant
•
r4055
Current referenced input value
•
p4056
Analog inputs type
•
p4057
Analog inputs, characte
ristic value x1
•
p4058
Analog inputs, characteristic value y1
•
p4059
Analog inputs, characteristic value x2
•
p4060
Analog inputs, characteristic value y2
•
p4063
Analog inputs offset
Note
Delivery condition
In the factory setting and after basic commissioning, an input current of 20 mA is equal to the
main setpoint 100% reference speed (p2000), which has been set to the maximum speed
(p1082).
Example: Switching analog input 0 from current to voltage input –10 to +10 V
Current/voltage switchover
Set current/voltage selector to "Voltage" ("V").
Set analog input type 0 to
-10 ... +10 V.
Note
Save changes so that they are protected against power failure
The change to the analog input m
ust then be stored on the CompactFlash card so that it is
protected in the event of a power failure.