Operation
6.7 Communication according to PROFIdrive
Converter cabinet units
324 Operating Instructions, 07/2016, A5E03347396A
The following options are available for reading and writing parameters:
● S7 protocol
The STARTER commissioning tool use this protocol, for example, in the online mode via
PROFIBUS.
● PROFIdrive parameter channel with the following data records:
– PROFIBUS: Data block 47 (0x002F)
The DPV1 services are available for master class 1 and master class 2.
– PROFINET: Data block 47 and 0xB02F as global access, data block 0xB02E as local
access
Note
References
Please refer to the following documentation for a detailed description of acyclic
communication:
Reference: PROFIdrive Profile V4.1, May 2006, Order No: 3.172
PROFIBUS DP, addressing is carried out via the logical address or the diagnostics
address.
PROFINET IO, addressing is carried out exclusively via a diagnostics address that is
assigned to a module starting from slot 1. Parameters cannot be accessed using slot 0.