Operation
6.7 Communication according to PROFIdrive
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
341
The other diagnostics data (types) can be in any sequence. This is the reason that the
following diagnostics data include a header:
● Identifier-related diagnostics
● Status messages/module status
● Channel-related diagnostics
The diagnostic data type can be uniquely identified based on the header.
Note
The master must operate in the DPV1 mode.
For communication via PROFIBUS, standard diagnostics is structured as follows.
1 Station
status 1
Master_
Lock
= 0
Prm_Fault 0 Not_
Supported
Cfg_Fault Station_
Not_
Ready
Station_
Non_
Exist
2 Station
0 0 Sync_
Freeze_
WD_On 1 Stat_Diag
Prm_Req
3 Station
status 3
0 0 0 0 0 0 0
Ident_Number (HighByte) of the slave
Ident_Number (LowByte) of the slave
In this context, the following values are decisive for diagnostics:
● Ext_Diag
– Group signal for diagnostics in the slave
– = 1, if at least 1 alarm is active
● Ext_Diag_Overflow
Display, diagnostics overflow in the slave (for more than 240 bytes)