EasyManua.ls Logo

Siemens SINAMICS G150 - Page 368

Siemens SINAMICS G150
680 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
6.9 Communication via PROFINET IO
Converter cabinet units
368 Operating Instructions, 07/2016, A5E03347396A
I&M parameters
Table 6- 31 Parameter designation, assignment and meaning
I&M parameter des-
ignation
For-
mat
Size/
octets
Initialization
SINAMICS
parameters
Meaning
I&M 0:
IM_SUPPORTED
- - - r8820[62,63] The parameter indicates which I&M data sets
are supported.
The value 0x1E indicates that I&M data sets
1...4 are available.
I&M 1:
TAG_FUNCTION
Visible
string
32 Space
0x20…0x20
p8806[0...31] Text that identifies the function or task of the
device.
I&M 1:
TAG_LOCATION
Visible
string
22 Space
0x20…0x20
p8806[32...53
]
Text that identifies the device location.
I&M 2:
INSTALLATION_
DATE
Visible
string
16 Space
0x20…0x7E
p8807[0...15] Text with the date of the installation or the
initial commissioning of the device. The follow-
ing date formats are supported:
• YYYY-MM-DD
• YYYY-MM-DD hh:mm
– YYYY: Year
– MM: Month 01...12
– DD: Day 01...31
– hh: Hours 00...23
– mm: Minutes 00...59
The separators between the individual specifi-
cations, i.e. hyphen '-', blank ' ' and colon ':',
must be entered.