Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
457
Figure 7-19 Speed controller with droop
Precondition
All connected drives must be operated with vector and speed control (with or without
speed actual value encoder).
The setpoints at the ramp function generators of the mechanically connected drives must
be identical; the ramp function generators must have identical ramp-up and ramp-down
times.
Function diagram
FP 6030
Speed setpoint, droop
Parameters
r0079
Total speed setpoint
r1482
Speed controller I torque output
p1488
Droop input source
p1489
Droop feedback scaling
r1490
Droop feedback speed reduction
p1492
Dr
oop feedback enable
r1508
Torque setpoint before supplementary torque