Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
459
Monitoring of the speed deviation between motor model and external speed
The external actual speed (r1443) is compared with the actual speed of the motor model
(r2169). If the deviation is greater than the tolerance threshold set in p3236, after the switch-
off delay time set in p3238 expires, fault F07937 (Drive: Speed deviation motor model to
external speed) is generated and the drive switched-off corresponding to the set response
(factory setting: OFF2).
Figure 7-20 Monitoring "Speed deviation model / external in tolerance"
Vector control – speed controller with/without encoder
Signals and monitoring function – Torque messages, motor blocked/stalled
r0063[0]
Actual speed value unsmoothed
p1440
Speed controller actual speed value
p1442
Speed controller actual speed value smoothing time
r1443
CO: Speed controller actual speed value at actual value input
p1452
Speed controller actual speed value smoothing time (without encoder)
r2169
l speed value smoothed messages
r2199.7
Speed deviation model / external in tolerance
p3236
p3237
p3238
-off delay n_act_motor model = n_act_external