Functions, monitoring, and protective functions
9.2 Drive functions
Converter cabinet units
528 Operating Instructions, 07/2016, A5E03347396A
Adapting the pump, fan, or compressor characteristic
The 5 interpolation points of the pump, fan, or compressor characteristic are entered using
parameters p3320 to p3329. This characteristic can be configured individually for each drive
data set.
Table 9- 6 Interpolation points of the pump, fan, or compressor characteristic
Factory setting:
P: Power in %
n: Speed in %
1
p3321 n1 = 0.00
2
3
4
5
Note
Consequences of not adjusting the pump, fan, or compressor curve
If the interpolation
points of the pump, fan, or compressor curve are not adapted, the factory
setting will be used to calculate the energy saving indicator. The values of the factory setting
could then deviate from the equipment characteristic and cause incorrect calculation
of the
The energy saving is displayed in parameter r0041.
By setting p0040 = 1, the value of parameter r0041 is reset to 0. Parameter p0040 is then
automatically set to 0.