Loading...
Functions, monitoring, and protective functions
9.2 Drive functions
Converter cabinet units
542 Operating Instructions, 07/2016, A5E03347396A
Activation/configuration
The web server is already active in the factory settings.
The web server is configured via parameter p8986 (web server configuration).
Data transfer
Access is performed by unsecured (http) or secured transmission (https).
The type of transmission is defined by entering the corresponding address.
For safety reasons, secure transmission can be forced by deactivation of the http port.
Access
The web server is accessed via the following interfaces:
LAN interface of the Control Unit CU320-2 DP or CU320-2 PN
PROFINET interface of the CU320-2 PN
Addressing of the drive is based on the IP address.
The IP address can be taken from the following parameters.
Integrated Ethernet interface (LAN interface): r8911[0...3]
PROFINET interface: r8931[0...3]
Access rights
There are two users, who have different authorizations:
User "SINAMICS" (activated in the factory setting):
Calling diagnostics pages
Resetting the fault memory
Creating/expanding/removing parameter lists
Reading/writing/saving parameters
User "Administrator," additionally:
Updating the configuration
Updating the firmware
Loading user-defined pages to the drive
The settings of the write and know-how protection also apply to the drive parameters and
configuration when accessing the web server.