5 Operation
5.4 Configuration modes
Manual
SIPART DR21
C73000-B7476-C143-08
167
Structure
switch
switch
posi-
tion
Function
S9 Thermocouple type AI3 (slot 1) with UNI--module (only active at S8=1/2)
[0] Type L
1 Type J
2 Type K
3 Type S
4 Type B
5 Type R
6 Type E
7 Type N
8 Type T
9 Type U
10 any type (without linearization)
s
S10 Temperature unit AI3 (slot 1) with UNI--module (only ac tive at S8=1/2/3/4/5)
p
uts
[0] Degrees Celsius
inp
u
1 Degrees Fahrenheit
l
og i
n
2 Kelvin
Anal
o
S11
S12
S13
S14
Root extraction AI1 to AI4
no yes
AI1 [0] 1
AI2 [0] 1
AI3 [0] 1
AI4 [0] 1
S15
S16
S17
S18
S19
S20
Assignment of x1, x2, x3, yN, yR, z from AI1A to AI4A
0 % AI1A AI2A AI3A AI4A
x1 0[1]234
x2 0 1 [2] 3 4
x3/we 0 1 2 [3] 4
y
N
0123[4]
y
R
[0]1234
z [0]1234
S21 Assignment of the linearizer (see ofPA) open
[0] none
uts
1 AI1
inp
u
2 AI2
a
log i
n
3 AI3
An
a
4 AI4
A
5 x1
S22 Assignment slot 3
[0] not used
3
1 4DO/2DI (DO3--DO6/DI3,DI4)
4DO/1DI (DO3--DO6/DI3,DI4=0)
S
lot
3
2 5DI (DI3--DI7)
Sl
3 2 relays (DO3, DO4)