Configuration
6.9 Switching of capacitive loads
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
113
Table 6- 2 Max. switching frequency z in operating cycles/hour
at I
e
/AC-6b and at various operational voltages
1)
230 V,
50/60 Hz 1/h
180 180 100 100 100 100 100 200 150
400 V,
180 180 100 100 100 100 100/80
2)
100/80
2)
80/60
3)
480 V,
180 180 100 100 70 60 50 53 40
500 V,
180 180 100 100 65 55 45 53 40
600 V,
180 180 100 100 45 40 32 30 20
690 V,
180 150 100 72 36 30 25 30 20
1000 V,
--- --- --- --- --- --- --- 30 20
Information for worst case, higher switching frequency possible.
Operating cycles/h: 100 with AC operation; 80 with AC/DC operation
3)
Operating cycles/h: 80 with AC operation; 60 with AC/DC operation