8.2 Conductor cross-sections
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
240 Manual, 09/2017, A5E03656507120A/RS-AE/006
8.2.3
Conductor cross-sections for ring cable lug connection system
Conductor cross-sections for ring cable lug connection system
The tables below define the permissible conductor cross-sections for main terminals and
auxiliary conductor connections in sizes S00 and S0 for ring cable lug connection systems.
Table 8- 21 Main conductors and auxiliary conductors of size S00 with M3 combination screws
SIRIUS devices
Tool
Pozidriv size 2,
Ø 5 to 6 mm
Tightening torque
0.8 to 1.2 Nm
Ring cable lug
1)
d
2
= min. 3.2 mm
d
3
= max. 7.5 mm
Table 8- 22 Main conductors and auxiliary conductors of size S0 with M4 combination screws
SIRIUS devices
Tool
Pozidriv size 2,
Ø 5 to 6 mm
Tightening torque
2.0 to 2.5 Nm
Ring cable lug
1)
d
2
= min. 4.3 mm
d
3
= max. 12.2 mm