Configuration
6.11 Contactors in safety applications
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
125
6.11.2.4
P-switching fail-safe outputs
EMERGENCY STOP shutdown up to SILCL 3 or PL e / Cat. 4 via two F-DQs
Description
EMERGENCY STOP shutdown
"Detecting" subsystem up to SILCL 3 as per IEC 62061 and PL e / Cat. 4 as per
EN ISO 13849-1
EMERGENCY STOP command device according to ISO 13850
Two-channel sensor interfacing
Discrepancy evaluation between the sensor channels
Cross-circuit monitoring of the sensor wiring
Monitored start
Shutdown of two contactors via two safety-related outputs
Stop category 0
"Reacting" subsystem up to SILCL 3 as per IEC 62061 and PL e / Cat. 4 as per
EN ISO 13849-1
Redundant actuators
Use of two safety-related outputs on the 3SK1 safety relay when actuator cables are laid
unprotected in the field.