Configuration
6.11 Contactors in safety applications
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
118 Manual, 09/2017, A5E03656507120A/RS-AE/006
Contactors in safety applications
6.11.1
Note
SILCL 3 in accordance with IEC 62061:2005
PL e / Cat. 4 in accordance with EN ISO 13849-1:2015
The contactors with fail
-safe control input are designed in such a way as to allow
implementation of applications up to SILCL
3 in accordance with IEC 62061, PL e / Cat. 4 in
ISO 13849-1.
Safety functional extra-low voltage
Can Cause Death, Serious Injury, or Damage to Property
The fail-safe control input of these contactors is operated with a voltage of 24 V DC. A
power supply unit with safety extra-low voltage (SELV, PELV) must be used.
You can find more detailed information about safety functional extra-low voltage in the data
sheets of the power supplies to be used.
Hazardous Voltage
Will Cause Death, Serious Injury or Damage to Property.
Health hazard from automatic restart.
Check the safety functions after a short-circuit / overload.